Mounter and Service Provider

It’s time to expect more from your fire alarm!
All smoke detectors of the DOKA sensors series are resistant to dust ingress, as the sensing chamber is hidden under the housing and protected by fine grid. Dust settles in special compartments of the housing without reaching the camera. This allows the detectors to be used even in industrial environments
The enclosure of all DOKA smoke detectors is made with vertical and horizontal smoke inlets, which allows to catch the flow in any direction and quickly react to the first signs of fire

Installation of detectors of the DOKA sensors series

Все извещатели серии DOKA sensors устанавливаются в базу нестандартным способом с применением съемной группы контактов. Это позволяет подключать провода в любом удобном положении. Надежный закрытый разъем обеспечивает защиту и долговечность электрического контакта между базой и извещателем

The manufacturer’s many years of experience have allowed us to create products with maximum efficiency and low cost.

Key features of DOKA sensors:

Why do we recommend interactive mode?

Just 3 simple steps.

Any change in the “DOKA – c” states is displayed by light indication, and the control panel registers this change using basic signals: “AL (Alarm Loop) is normal”, “AL is open”, “Fire”.

If something occurs in the alarm loop, the control panel signals and registers it in the event log.

The staff on duty calls a representative of the service organization.

The specialist arrives at the facility and, according to the control panel event log, finds in which AL the occasion was registered.

By light indication of all “DOKA – c” in this AL, it must establish which of the alarm box is in a state different from the “Stand-by mode”.

You save your time and money by increasing quality and reliability:

  • there is no need to check each alarm box, since the system completely controls itself
  • you do not need to spend a lot of time looking for a faulty or triggered alarm box, because “DOKA – c” always remembers and displays its states
  • “Doka – c”, which diagnosed dust pollution or a faulty, will unobtrusively report this to the control panel no more than one time a day.

Any change in the “DOKA – c” states is displayed by light indication, and the control panel registers this change using basic signals: “AL (Alarm Loop) is normal”, “AL is open”, “Fire”.

If something occurs in the alarm loop, the control panel signals and registers it in the event log.

The staff on duty calls a representative of the service organization.

The specialist arrives at the facility and, according to the control panel event log, finds in which AL the occasion was registered.

By light indication of all “DOKA – c” in this AL, it must establish which of the alarm box is in a state different from the “Stand-by mode”.

You save your time and money by increasing quality and reliability:

  • there is no need to check each alarm box, since the system completely controls itself
  • you do not need to spend a lot of time looking for a faulty or triggered alarm box, because “DOKA – c” always remembers and displays its states
  • “Doka – c”, which diagnosed dust pollution or a faulty, will unobtrusively report this to the control panel no more than one time a day.

How does it work?

01
All detectors are in "Standby mode"
02
One of the detectors diagnosed dusty
03
Replace the detector and leave the facility
Interactive mode is activated by removing the jumper strap “3” and is possible if connection to the control panel is set according to the schemes below. If jumper strap “3” is set, then “DOKA – c” works with the control panel as an usual fire box.

Removal and installation into the base.

DOKA-c in your hands

Place your thumbs in the holesand push the base towards to the arrow.

DOKA-c on the ceiling.

Put your thumb on the indicated place on the fire box base and slide it towards to the arrow, like a matchbox.
If it is comfortable, this operation can be performed with both hands. The actions are similar.

DOKA-c in your hands

Place your thumbs in the holesand push the base towards to the arrow.

DOKA-c on the ceiling.

Put your thumb on the indicated place on the fire box base and slide it towards to the arrow, like a matchbox.
If it is comfortable, this operation can be performed with both hands. The actions are similar.

Mounting

Detachable multi-connector is convenient to connect in any position.
Connection of any cable with a conductor cross-section up to 1.5 mm2.

Mounting variants

Specifications

Optical smoke detector IP 212-02К “DOKA - c”

The detector is installed in enclosed spaces for continuous smoke detection and transmission of Fire and Fault signals to the fire control panel through a 2 wire loop

Certified:
BY: ТР 2009/013/BY, СТБ 11.16.03
RU: ГОСТ Р 53325-2012
UA: ДСТУ EN 54-7
ISO 9001

Detector sensitivity 0.05 - 0.20 dB / m
Average area controlled by one detector with a height of the protected room up to 3.5 m no more than 85 m2
Supply voltage range 9 ... 24 V
Rated supply voltage 12 V
Consumption current in "Standby mode" no more than 65 μA
Consumption current in the "Fire" state (set by the position of jumpers "1" and "2") 6 ± 1, 15 ± 1, 10 ± 1, 19 ± 2 milliampere
Duration of outage to reset the Fire condition more than 2 s
Permissible level of exposure to background illumination 12000 lx
The degree of protection of the detector shell according to GOST (National Standart) 14254 IP40
Operating temperature range - 30 ... + 55 °С
Relative air humidity at a temperature of +40 ± 2 ° С 93 ± 3 %
Climatic version according to GOST (National Srandart) 15150 УХЛ 3.1
Immunity to electromagnetic interference hardness 3
Weight of the detector with base no more than 0.14 kg
dimensions no more than 90 x 90 x 45 mm
Average service life at least 10 years

Self contained smoke detector IP 212-03К “DOKA - a

The detector is installed in enclosed spaces for continuous smoke
detection, powered by a built-in battery.
It has a fault indication and low battery signal.

Standards compliant:
RU: ГОСТ Р 53325-2012
EU: EN 14604
ISO 9001

Battery type 6F22
Current consumption in ‘‘Normal Operation’’ state max. 25 µA
Guaranteed battery operation 12 months
Sound pressure level min. 85 dB
IP rating IP40
Operating temperature range - 10 … + 55 °С
Relative humidity at +40 °C 93 %

Heat detector IP 101-13К-A2S “DOKA - T”

The detector is installed in enclosed spaces for continuous heat rise detection and transmission of Fire and Fault signals to the fire control panel through a 2 wire loop

Standards compliant:
BY: ТР 2009/013/BY, СТБ 2218
EU: EN 54-5
ISO 9001

Detector clas А2S
State “Fire” temperature +54 … +70 °С
Supply voltage range 9 … 24 VDC
Current consumption in “Normal Operation” state max. 50 µA
Current consumption in “Fire” state set from: 5, 10, 15, 20 mA
IP rating IP40
Operating temperature range - 30 … + 75 °
Relative humidity at +40 °C 93 %

Combines optical smoke and heat detector IP 212/101-12К-A2M “DOKA - CT”

The detector is installed in enclosed spaces for continuous smoke and heat detection and transmission of Fire and Fault signals to
the fire control panel through a 2 wire loop

Standards compliant:
BY: ТР 2009/013/BY, СТБ 11.16.03, СТБ 2218
EU: EN 54-7, EN 54-5
ISO 9001

Detector clas А2M
State “Fire” temperature +54 … +70 °С
Supply voltage range 9 … 24 VDC
Current consumption in ”Normal Operation” state max. 65 µA
Current consumption in ”Fire” state set from: 5, 10, 15, 20 mA
IP rating IP40
Operating temperature rang - 30 … + 75 °
Relative humidity at +40 °C 93 %

Optical smoke detector IP 212-02К “DOKA - c”

The detector is installed in enclosed spaces for continuous smoke detection and transmission of Fire and Fault signals to the fire control panel through a 2 wire loop

Certified:
BY: ТР 2009/013/BY, СТБ 11.16.03
RU: ГОСТ Р 53325-2012
UA: ДСТУ EN 54-7
ISO 9001

Detector sensitivity 0.05 - 0.20 dB / m
Average area controlled by one detector with a height of the protected room up to 3.5 m no more than 85 m2
Supply voltage range 9 ... 24 V
Rated supply voltage 12 V
Consumption current in "Standby mode" no more than 65 μA
Consumption current in the "Fire" state (set by the position of jumpers "1" and "2") 6 ± 1, 15 ± 1, 10 ± 1, 19 ± 2 milliampere
Duration of outage to reset the Fire condition more than 2 s
Permissible level of exposure to background illumination 12000 lx
The degree of protection of the detector shell according to GOST (National Standart) 14254 IP40
Operating temperature range - 30 ... + 55 °С
Relative air humidity at a temperature of +40 ± 2 ° С 93 ± 3 %
Climatic version according to GOST (National Srandart) 15150 УХЛ 3.1
Immunity to electromagnetic interference hardness 3
Weight of the detector with base no more than 0.14 kg
dimensions no more than 90 x 90 x 45 mm
Average service life at least 10 years

Self contained smoke detector IP 212-03К “DOKA - a

The detector is installed in enclosed spaces for continuous smoke
detection, powered by a built-in battery.
It has a fault indication and low battery signal.

Standards compliant:
RU: ГОСТ Р 53325-2012
EU: EN 14604
ISO 9001

Battery type 6F22
Current consumption in ‘‘Normal Operation’’ state max. 25 µA
Guaranteed battery operation 12 months
Sound pressure level min. 85 dB
IP rating IP40
Operating temperature range - 10 … + 55 °С
Relative humidity at +40 °C 93 %

Heat detector IP 101-13К-A2S “DOKA - T”

The detector is installed in enclosed spaces for continuous heat rise detection and transmission of Fire and Fault signals to the fire control panel through a 2 wire loop

Standards compliant:
BY: ТР 2009/013/BY, СТБ 2218
EU: EN 54-5
ISO 9001

Detector clas А2S
State “Fire” temperature +54 … +70 °С
Supply voltage range 9 … 24 VDC
Current consumption in “Normal Operation” state max. 50 µA
Current consumption in “Fire” state set from: 5, 10, 15, 20 mA
IP rating IP40
Operating temperature range - 30 … + 75 °
Relative humidity at +40 °C 93 %

Combines optical smoke and heat detector IP 212/101-12К-A2M “DOKA - CT”

The detector is installed in enclosed spaces for continuous smoke and heat detection and transmission of Fire and Fault signals to
the fire control panel through a 2 wire loop

Standards compliant:
BY: ТР 2009/013/BY, СТБ 11.16.03, СТБ 2218
EU: EN 54-7, EN 54-5
ISO 9001

Detector clas А2M
State “Fire” temperature +54 … +70 °С
Supply voltage range 9 … 24 VDC
Current consumption in ”Normal Operation” state max. 65 µA
Current consumption in ”Fire” state set from: 5, 10, 15, 20 mA
IP rating IP40
Operating temperature rang - 30 … + 75 °
Relative humidity at +40 °C 93 %